RCT-Y Copper Air Core Coils, Rigid Rogowski coil CT
Advantages
l Simple to install(especially in limited space)
l Wide dynamic current range
l No magnetic saturation
l No open circuit danger,No overload danger,Intrinsically safe.
l Wide bandwidth
l Low current measurable
l High protection class IP65
rogowski current transformer
Applications
l Power meters
l Power quality monitoring
l Condition monitoring
l Distributed measurement systems.
l Electric furnace
l Harmonic management
l Relay Protection
l Grounding current monitoring
rogowski current transformer
Specification
MODEL |
FCT-Y-200 |
FCT-Y-250 |
FCT-Y-300 |
FCT-Y-350 |
FCT-Y-400 |
||
Coil length |
200mm |
250mm |
300mm |
350mm |
420mm |
||
Window size |
60mm |
75mm |
90mm |
105mm |
120mm |
||
Coil Diameter |
8mm |
||||||
Lead length |
2meter |
||||||
Rated current |
100A,200A 300A,500A 600A,750A |
300A,400A 500A,600A 750A,1kA |
400A,500A 600A,750A 1kA,1.5kA |
500A,600A 750A,1kA 1.5kA,2kA |
750A,1kA 1.5kA,2kA 2.5kA,3kA |
||
Output (di/dt) |
50 mV/1000A @ 50 Hz 60 mV/1000A @ 60 Hz
|
55 mV/1000A @ 50 Hz 66 mV/1000A @ 60 Hz |
60mV/1000A @ 50 Hz 72 mV/1000A @ 60 Hz |
65mV/1000A @ 50 Hz 78 mV/1000A @ 60 Hz |
90mV/1000A @ 50 Hz 108 mV/1000A @ 60 Hz |
||
Accuracy |
<1% typical at 20% to 120% of rated current (most accurate position, 25℃) |
||||||
Phase error |
≤0.5° |
||||||
Linearity |
±0.2% of reading(10% to 100% of range) |
||||||
Bandwidth |
2Hz to 1MHz(-3dB) |
||||||
Operating temperature |
-20℃ to 70℃ |
||||||
Storage temperature |
-30℃ to 90℃ |
||||||
Other requirements,please contact us to OEM. |
« Fault indicator rogowski coil Three-in-one Flexible Rogowski Coil »