Sensor Mod.
|
CHB-50P、CHB-100P Closed-loop Hall Current Transducer
|
Description
|
The SENSOR Module CHB-50P, 100P is a closed loop Hall current sensor to measure 50A…100ADC, AC or pulsed currents with a galvanic isolation between the primary and secondary circuits.
|
|
Closed-loop Hall Current Sensor:
|
Type
|
Nominal current
|
Output current
|
Accuracy
|
Supply voltage
|
Aperture
|
IN(A)
|
IM(mA)
|
X(%)
|
Vc(V)
|
mm
|
CHB-50P
|
50
|
50
|
±1.0%
|
±12…15
|
φ10
|
CHB-100P
|
100
|
100
|
±0.8%
|
±12…15
|
φ10
|
|
Specifications:
|
Principle
|
Closed loop Hall effect principle
|
Input current
|
50…100A(DC、AC、Pulsed current)
|
Output current
|
50mA/100mA
|
Turns ratio
|
1:1000
|
Frequency
|
DC~100KHz
|
Accuracy
|
±0.8%...1.0%
|
Response time
|
<1μS
|
Linearity
|
<0.1%
|
Supply voltage
|
±12V…15V(±5%)
|
Consumption
|
10mA+IM(Output current)
|
Isolation voltage
|
Between primary and secondary circuit: 3KV RMS/50Hz/1min.
|
Operating temp.
|
0…+70℃
|
Applications
|
The sensors are used in the industry field of power supplies, welding machines, converters,
|
|
industry auto-control, motor drives, electronic power system, railways, rectifiers systems etc.
|
|
Dimensions(mm) & Connection:
|
|
|
Typical Applications:
|
|
Primary current IN and Output IM:
It is isolated between the primary current IN and the secondary output current IM.
The linearity is better than 0.1%.
Type: CHB-50P/CHB-100P
Nominal current: IN=50A/100A
Output current: IM=100mA
Supply voltage: Vc=±15V
Measuring resistance: RM=0Ω
|
|