Sensor Mod. |
CHB-50A、CHB-100A Closed-loop Hall Current Transducer |
||||||
Description |
The SENSOR Module CHB-50A, 100A is a closed loop Hall current sensor to measure 50A…100ADC, AC or pulsed currents with a galvanic isolation between the primary and secondary circuits. |
||||||
|
|||||||
Closed-loop Hall Current Sensor: |
|||||||
Type |
Nominal current |
Output current |
Accuracy |
Supply voltage |
Aperture |
||
IN(A) |
IM(mA) |
X(%) |
Vc(V) |
mm |
|||
CHB-50A |
50 |
50 |
±0.8% |
±15 |
15x7 |
||
CHB-100A |
100 |
50 |
±0.5% |
±15 |
15x7 |
||
|
|||||||
Specifications: |
|||||||
Principle |
Closed loop Hall effect principle |
||||||
Input current |
50…100A(DC、AC、Pulsed current) |
||||||
Output current |
50mA |
||||||
Turns ratio |
1:1000(50A);1:2000(100A) |
||||||
Frequency |
DC~100KHz |
||||||
Accuracy |
±0.5%...0.8% |
||||||
Response time |
<1μS |
||||||
Linearity |
<0.1% |
||||||
Supply voltage |
±15V(±5%) |
||||||
Consumption |
10mA+IM(Output current) |
||||||
Isolation voltage |
Between primary and secondary circuit: 2.5KV RMS/50Hz/1min. |
||||||
Operating temp. |
-25…+85℃ |
||||||
Applications |
The sensors are used in the industry field of power supplies, welding machines, converters, |
||||||
|
industry auto-control, motor drives, electronic power system, railways, rectifiers systems etc. |
||||||
|
|||||||
Dimensions(mm) & Connection: |
|||||||
|
|||||||
|
|||||||
Typical Applications: |
|||||||
|